Click
on drawing to view large scale version
|
| |
| SmartFan
AC-3NA is available for 115 or 230 VAC PSC or shaded pole
fans and blowers with current ratings up to 6.0 Amps. AC-3NA
operates at either 50 or 60 HZ power line frequency as selected
by a jumper on the board. It includes a temperature alarm, triggered
if the sensor temperature reaches 10°C above the Control Temperature.
AC-3NA is compatible with temperature sensors P1 through P9
shown on the sensors
page. |
| |
|
Features
- Temperature
alarm from optically isolated NPN transistor
- Three-second
duration start pulse for rapid and sure fan starting
- Fail-safe, automatic
speed switch-up if sensor signal is lost
- Compatible with
both PSC and Shaded Pole fan motors
|
| |
UL recognized, File E100344 |
CSA approved, File LR69458 |
IEC 950 and VDE 0806 approved TUV Rheinland File E77132 |
| |
| SPECIFICATIONS |
| |
|
Part
Number
|
Power
Line Voltage
|
Maximum
Current to Fans (1)
|
Control
Temperature
|
|
Nominal
|
Range
|
200
ft/min
|
Still
Air
|
Air
Sensor
|
P3
Surface Sensor
|
|
|
115
VAC
|
95-135
VAC
|
6.0
Amps
|
3.0
Amps
|
|
|
|
|
230
VAC
|
190-270
VAC
|
6.0
Amps
|
3.0
Amps
|
|
|
|
H101
|
Hardware
Pack
|
|
| (1)
Air Temperature of 55°C or less. |
| |
| INSTALLATION |
| |
|
Mounting
|
| To satisfy
safety agency requirements (UL, CSA, IEC, VDE), allow 1/4" (6.3
mm) between the circuit board and chassis ground and 5/16” (8
mm) to any uninsulated secondary circuits. To satisfy UL, a
normal blow fuse rated 10 Amps or less should be used in the
power line circuit. |
| |
| Sensor
Selection |
| Click
here to view Sensors page. There is no polarity consideration
when connecting the thermistor. |
| |
| CONNECTIONS
/ JUMPERS |
|
|
Figure
1 Wiring Diagram Click on drawing
to view large scale version
|
|
| |
| |
| SUGGESSTED
CONECTING HARDWARE |
|
|
|
Ref.
Desc.
|
Header
on Board (1)
|
H101
Hardware Pack
|
|
|
Quantity
|
Description
|
Manufacturer
(1)
|
PartNumber
(1)
|
|
J1
|
39-28-1043
|
|
Housing
Terminal (tin)
|
|
|
|
J2
|
22-29-2021
|
|
Housing
Terminal(gold)
|
|
|
|
J3
|
22-29-2021
|
|
Housing
Terminal(gold)
|
|
|
|
|
4
|
PCB Support
|
Richco
|
CBS-4-19
|
|
| (1)
or equivalent |
| |